Gas Furnace Technician Repair Chart
York / Coleman Gas Furnace Sequence of Operation Flow Chart
Thermostat calls for heat ↓
Inducer motor starts (establishes draft) ↓
Pressure switch proves draft (safety check) ↓
Ignition sequence begins (hot surface ignitor or spark) ↓
Gas valve opens ↓
Burner ignition ↓
Flame sensor proves flame ↓
Blower motor starts after delay ↓
Furnace runs until thermostat is satisfied ↓
Gas valve closes & burners shut off ↓
Blower runs post‑purge (clears residual heat/gases) ↓
Blower shuts off → Cycle complete
If at any point the furnace quits during operation the first thing to check is the control board to see if there are any LED lights blinking on it --> See Flash Code Chart
Coleman / York Furnace Flash Code Chart
|
Flash Code |
Result (Meaning) |
Fix (Recommended Action) |
|
Slow Green Flash |
Normal operation |
No action needed |
|
Slow Amber Flash |
Normal operation with call for heat |
No action needed |
|
Rapid Red Flash |
Twinning error, incorrect 24V phasing |
Check twinning wiring |
|
Rapid Amber Flash |
Flame sense current < 1.5 µA |
Clean flame sensor, check gas flow, verify >1.5 µA at test pad |
|
4 Amber Flashes |
Y signal from thermostat without G signal |
Correct thermostat wiring |
|
1 Red Flash |
Flame sensed with no call for heat |
Check gas valve for leaks or slow closing |
|
2 Red Flashes |
Pressure switch stuck closed |
Inspect/replace pressure switch, check wiring |
|
3 Red Flashes |
Pressure switch failed to close after inducer energized |
Check inducer, vent pipe, hose, or pressure switch |
|
4 Red Flashes |
Limit switch open |
Check filter, duct sizing, blower speed, firing rate, blower motor; also check fuse on board |
|
5 Red Flashes |
Rollout switch open |
Reset rollout, check combustion air, inducer, heat exchanger, burners; cycle power after reset |
|
6 Red Flashes |
Pressure switch opened 4 times during heat call |
Inspect pressure switch, venting, inducer; furnace locks out for 1 hr then retries |
|
7 Red Flashes |
Flame not established after 3 tries |
Check gas pressure, gas valve, flame sensor, ignitor, burners |
|
8 Red Flashes |
Flame lost 5 times during cycle |
Inspect gas pressure, flame sensor, gas valve |
|
9 Red Flashes |
Reversed line voltage polarity or grounding problem |
Verify polarity, grounding, flame probe not shorted |
|
10 Red Flashes |
Flame sensed with no call for heat |
Inspect gas valve and wiring |
|
11 Red Flashes |
Limit switch open >5 minutes (hard lockout) |
Likely failed blower motor or wheel; cycle 24 VAC power after correction |
|
12 Red Flashes |
Open igniter circuit |
Check for loose/disconnected wire or cracked igniter |
|
Steady On Red |
Control failure |
Replace control board |
|
60-Minute Auto Reset |
Watchdog resets lockout after 60 minutes |
Temporary protection; correct underlying issue |
|
Flame Sense Levels |
Normal ~3.7 µA DC; warning <1.5 µA; lockout <0.1 µA |
Verify flame sensor current, clean/replace sensor if low |