01-0843 Nordyne OEM sequencer 2 timings 4 switches H1-110 C1-110
01-0843 Nordyne OEM sequencer 2 timings 4 switches H1-110 C1-110
Product Description
The 01-0843 Heat Sequencer is a genuine OEM replacement sequencer designed for select Nordyne®, Intertherm®, Miller®, Frigidaire®, Gibson®, and Tappan® electric furnaces and air handlers. Featuring 2 timing functions and 4 switching circuits, this sequencer stages electric heat elements and blower operation to reduce electrical demand during startup while ensuring efficient heating performance.
Engineered to OEM specifications, the 01-0843 sequencer helps provide smooth activation and deactivation of electric heating circuits for dependable system operation.
Features
- Genuine OEM Nordyne replacement part
- 2 timing sequences
- 4 switching circuits
- H1-110 / C1-110 timing configuration
- Controls staged heater operation
- Reduces electrical inrush current
- Reliable electric furnace performance
- Direct replacement for compatible equipment
Technical Notes
- Part Number: 01-0843
- Product Type: Heat Sequencer
- Timing Functions: 2
- Number of Switches: 4
- Timing Designation: H1-110 / C1-110
- Application: Electric Furnaces and Air Handlers
- Function: Sequential control of electric heat strips and blower circuits
- OEM Replacement Component
- Verify timing specifications and terminal configuration before ordering
- Professional installation recommended
Cross Reference
- 01-0843
- 010843
- Nordyne Heat Sequencer
- Electric Furnace Sequencer
- H1-110 C1-110 Sequencer
- 4 Switch Heat Sequencer
- HVAC Heat Sequencer
- Electric Heat Control Sequencer
- Furnace Sequencer Relay
Fits Models
Compatible with many electric furnaces and air handlers manufactured by:
- Nordyne®
- Intertherm®
- Miller®
- Frigidaire®
- Gibson®
- Tappan®
Used in numerous electric furnace and heat strip applications. Verify equipment model number, sequencer timing, and terminal configuration before ordering.
On a typical electric furnace, the blower motor is hooked to terminals M1 & M2 (perhaps referred to as H1 & H2 on other various sequencers). The heating elements are then hooked to M3-M4 and M5-M6 and M7-M8, (25 Amp Load) do not over power by connecting more than 1 element per switch
24V feeds the bottom (gold) terminals of the sequencer. Welded jumper bars connect the 24V from one tower to the next. If your application does not use these jumpers, simply twist them off with a pliers. 
Not all the terminals of the sequencer may be used in your application. In some cases, you may need extra terminals. If that happens, included are extra terminal adapters to convert one terminal to two.
Â